Cool/Heat Min On/Off
These items are used to limit the on and off times of the cooling and heating system (in minutes).
Cool Minimum On
The number of minutes the thermostat forces the cooling system to remain on
before turning off. Raising this number will increase the total time the cooling
system is on (saving energy), but may allow the temperature to drift farther from
setpoint (decreasing comfort). When combined with Cool Minimum Off, cycles per
hours can be obtained by using the following calculation:
60 / (Cool Minimum On + Cool Minimum Off). The default time is 6 minutes.
Cool Minimum Off
The number of minutes the thermostat forces the cooling system to remain off
before starting again. Raising this number will increase the total time that the
cooling system is off (saving energy), but may allow the temperature to drift farther
from the setpoint (decreasing comfort). When combined with Cool Minimum On,
cycles per hours can be obtained by using the following calculation:
60 / (Cool Minimum On + Cool Minimum Off). The default time is 6 minutes.
Heat Minimum On
The number of minutes the thermostat forces the heat to remain on before turning
off. Raising this number will increase the total time the heating system is on
(saving energy), but may allow the temperature to drift farther from the setpoint
(decreasing comfort). When combined with Heat Minimum Off, cycles per hours
can be obtained by using the following calculation:
60 / (Heat Minimum On + Heat Minimum off). The default time is 6 minutes.
Heat Minimum Off
The number of minutes the thermostat forces the heat to remain off before starting
again. Raising this number will increase the total time that the heating system is off
(saving energy), but may allow the temperature to drift farther from the setpoint
(decreasing comfort). When combined with Heat Minimum On, cycles per hours
can be obtained by using the following calculation:
60 / (Heat Minimum On + Heat Minimum off). The default time is 6 minutes.
Stage Settings
Note: Before operating the thermostat, the “Cool Stages” and “Heat Stages” must be configured.
The thermostat can be configured with the following stage settings:
Cool Stages
The number of cool stages the HVAC system can support. The default setting is 1.
Heat Stages
The number of heat stages the HVAC system can support. Auxiliary heat is
included in this number for heat pumps. The default setting is 1.
EEC Control
The EEC Settings are used to configure Energy Efficient Control, Cool Anticipator, 2
nd
Stage Differential, and
Auxiliary Heat Differential. Not all of these features apply to all thermostat configurations. Only the features
that apply to the current configuration (based on the System Type and Stage Settings) of the thermostat will be
available when this menu is selected.